Back
NEW

Batterie 12V 17Ah

ref. BAT12V17A

Specifications

Nominal voltage (V) : 12

20-hr rate Capacity to 10.5V at 20°C (Ah) : 17

10-hr rate Capacity to 10.8V at 20°C (Ah) : 15.7

Dimensions
Length (mm) : 181 (±1)
Width ( mm) : 76 (±1)
Height ( mm) : 167 (±2)
Mass (kg) : 6.1

Terminal Type

Threaded terminal - (M=Male or F=Female) Torque (Nm) : M5 (F) 2.45

Operating Temperature Range

Storage (in fully charged condition) : -20°C to +60°C

Charge : -15°C to +50°C

Discharge : -20°C to +60°C

Storage

Capacity loss per month at 20°C (% approx.) : 3

Case Material

Standard : ABS (UL94:HB)

FR version available : UL94:V0

Charge Voltage

Float charge voltage at 20°C (V)/Block : 13.65 (±1%)

Float charge voltage at 20°C (V)/Cell : 2.275 (±1%)

Float Chg voltage tmp correction factor from std 20°C (mV) : -3

Cyclic (or Boost) charge Voltage at 20°C (V)/Block : 14.5 (±3%)

Cyclic (or Boost) charge Voltage at 20°C (V)/Cell : 2.42 (±3%)

Cyclic Chg voltage tmp correction factor from std 20°C (mV) : -4

Charge Current

Float charge current limit (A) : No limit

Cyclic (or Boost) charge current limit (A) : 4.25

Maximum Discharge Current

1 second (A) : 500

1 minute (A) : 150

Short-Circuit Current & Internal Resistance

Internal resistance - according to EN IEC 60896-21 (mΩ) : 34.47

Short-Circuit current - according to EN IEC 60896-21 (A) : 421

Impedance
Measured at 1 kHz (mΩ) 15

 

 

 

 

Dimensions (W x H x D) 181 x 167 x 76
Weight 6.1 Kg
Need information ?Contact our team
Available accessories (option)
Back